| 4 Hour |
3 Hour |
These opening are in walls that separate building or divide a single building into designated fire areas. |
| 2 Hour |
1-1/2 Hour |
Openings of this type are used in enclosures of vertical communication or egress through buildings. Examples of these types include stairwells and elevator shafts |
| 1 Hour |
1 Hour |
These door assemblies divide occupancies in a building. |
| 1 Hour |
1/4 Hour |
For use where there are openings in corridors or room partitions. |
| 2 Hour |
1-1/2 Hour |
This openings is in a wall where there is the potential for severe fire exposure from the exterior of the building. |
| 1 Hour |
1/4 Hour |
This opening is in an exterior wall that has the potential to be exposed to moderate to light fire from the exterior of the building. |
| 1 Hour |
1/3 Hour |
These openings are in corridors where smoke and draft control is required. The minimum opening is 1 Hour. |