Wall Rating | Door Rating | Description and Use |
4 Hour | 3 Hour | These opening are in walls that separate building or divide a single building into designated fire areas. |
2 Hour | 1-1/2 Hour | Openings of this type are used in enclosures of vertical communication or egress through buildings. Examples of these types include stairwells and elevator shafts |
1 Hour | 1 Hour | These door assemblies divide occupancies in a building. |
1 Hour | 1/4 Hour | For use where there are openings in corridors or room partitions. |
2 Hour | 1-1/2 Hour | This openings is in a wall where there is the potential for severe fire exposure from the exterior of the building. |
1 Hour | 1/4 Hour | This opening is in an exterior wall that has the potential to be exposed to moderate to light fire from the exterior of the building. |
1 Hour | 1/3 Hour | These openings are in corridors where smoke and draft control is required. The minimum opening is 1 Hour. |